Regulation 14

Part E – Operational Requirements

Operational readiness and maintenance

1   Purpose

The purpose of this regulation is to maintain and monitor the effectiveness of the fire safety measures the ship is provided with. For this purpose, the following functional requirements shall be met:

.1     fire protection systems and fire-fighting systems and appliances shall be maintained ready for use; and

.2     fire  protection  systems  and fire-fighting  systems  and appliances  shall  be properly tested  and inspected.

2.1   Operational readiness

2.1 .1 The following fire protection systems shall be kept  in good order so as to ensure their required performance if a fire occurs:

.1      structural  fire  protection,  including  fire-resisting  divisions,  and  protection  of  openings  and penetrations in these divisions;

.2     fire detection and fire alarm systems; and

.3    means of escape systems and appliances.

2.1 .2 Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. Portable extinguishers which have been discharged shall be immediately recharged or replaced with an equivalent unit.

2.2   Maintenance, testing and inspections

2.2 Maintenance, testing and inspections

2.2.1 Maintenance, testing and inspections shall be carried out based on the guidelines developed by the Organization and in a manner having due regard to ensuring the reliability of fire-fighting systems and appliances.

2.2.2 The maintenance plan shall be kept on board the ship and shall be available for inspection whenever required by the Administration.

2.2.3 The maintenance plan shall include at least the following fire protection systems and fire-fighting systems and appliances, where installed:

.1 fire mains, fire pumps and hydrants, including hoses, nozzles and international shore connections;

.2 fixed fire detection and fire alarm systems;

.3 fixed fire-extinguishing systems and other fire-extinguishing appliances;

.4 automatic sprinkler, fire detection and fire alarm systems;

.5 ventilation systems, including fire and smoke dampers, fans and their controls;

.6 emergency shutdown of fuel supply;

.7 fire doors, including their controls;

.8 general emergency alarm systems;

.9 emergency escape breathing devices;

.10 portable fire extinguishers, including spare charges; and

.11 fire-fighter’s outfits.

2.2.4 The maintenance programme may be computer-based.